Add this new subsection:

Where drains are not provided to prevent the accumulation of water in elevator pits, sumps are required. Drains connected directly to the sanitary system shall not be installed in elevator pits. Sumps in elevator pits, where provided, shall be covered and the cover shall be level with the pit floor. The pump shall be of sufficient capacity to prevent the accumulation of water in the pit. If the building is fire-sprinklered, the pump shall be sized of at least the capacity of one energized sprinkler head.

(Ord. 17-005 § 4, 2017)