Delete this section in its entirety, rename and replace with the following:

Section R303.3 Bathrooms and kitchens. Bathrooms, water closet compartments and similar rooms shall have a mechanical ventilating system connected directly to the outside capable of providing five air changes per hour. Moisture exhaust ducts shall be smooth and rigid. All moisture exhaust ducts located in an unconditioned space shall be insulated with a minimum R-11 and installed so as not to create low points where condensation may collect. All exhaust ducts shall be equipped with back-draft damper.

Kitchens shall have mechanical exhaust ventilation provided directly above or immediately adjacent to the primary cooking appliance. All vents shall be in accordance with IMC 2015.

(Ord. 17-005 § 4, 2017)