The tank, piping and valves for appliances burning oil shall be installed in accordance with the requirements of this chapter. The fuel oil supply line is required to be taken from the top of the tank only, and where the level of fuel within the tank may be above the inlet port of the appliance served an approved method to prevent siphoning from the tank must be provided. If the tank is located inside a building, emergency pressure relief venting is required to the exterior.